Auto-Extinguible type Nylon concentric cable 6 AWG 8 AWG 43 of through the pull experiment
Ⅰ Applications
The concentric cable is used as electric service entrance from the power distribution network until meter panel ,and as feeder cable from the meters panel until the panel or general distribution panel,just as it is specified in the National electric code,
This type of conductor can be used in dry and wet place,directly buried or outdoor;
It’s maximum temperature of operation is 70℃( PVC or PE insulation) or 90℃ (XLPE insulation) and it’s voltage of service for all the applications is 600V.
Ⅱ Specification
1. Conductor : Copper or Aluminum or 8000 series Aluminum Alloy
2. Insulation: PVC or PE or XLPE
3. Concentric neutral: Copper or Aluminum or 8000 series Aluminum Alloy
4. Sheath: PVC or PE or XLPE
Conductores concentricos de Aluminio
2×#6 | 3×#6 | 2×#4 | 3×#4 | 4×#4 | 3×#2 | 4×#2 | ||
Fase | No hilos | 7 | ||||||
Diametro hilo (mm) | 1.55 | 1.96 | 2.47 | |||||
Diametro fase (mm) | 4.66 | 5.88 | 7.42 | |||||
Seccion fase (mm2) | 13.3 | 21.2 | 33.6 | |||||
Espesor aislamiento (mm) |
1.14 | |||||||
Diametro sobre aislamiento (mm) | 6.94 | 8.16 | 9.70 | |||||
Neutro | Cobertura (%) | ≥90 | ||||||
No hilos | 25 | 65 | 26 | 65 | 103 | 65 | 103 | |
Diametro hilo (mm) | 0.81 | 0.51 | 1.02 | 0.64 | 0.51 | 0.81 | 0.64 | |
AWG | 20 | 24 | 18 | 22 | 24 | 20 | 22 | |
Seccion (mm2) | 12.97 | 13.33 | 21.3 | 21.11 | 21.12 | 33.7 | 33.44 | |
Espesor cubierta (mm) | 1.14 | 1.52 | 1.14 | 2.03 | 1.52 | 2.03 | 2.03 | |
Diametro exterior aproximado (mm) | 11.14 | 11.2×18.2 | 12.7 | 13.8×21.9 | 22 | 15.6×25.3 | 26 |