Introduction
ZXKC-HC high-voltage switch comprehensive characteristic tester is based on "High-voltage AC Circuit Breaker" GB1984-2003 as the design model, referring to the People's Republic of China power industry standard "High Voltage Test Equipment General Technical Conditions" Part 3, DL / T846.3- 2004 is a design basis, which provides convenience for dynamic analysis of various circuit breakers, and can accurately measure the mechanical dynamic parameters of low voltage, high oil, vacuum, sulfur hexafluoride and other high voltage circuit breakers of various voltage levels. The high-voltage circuit breaker is responsible for the dual tasks of control and protection in the power system, and its performance is directly related to the safe operation of the power system. The mechanical characteristic parameter is one of the important parameters to judge the performance of the circuit breaker.
Features
1. 8.4-inch color large screen, Windows operating system, user-friendly operation interface, intuitive interface, touch screen, easy to use by on-site operators.
2. High-speed thermal printer, convenient for printing test data on site.
3. The integrated operation power supply in the machine does not require on-site secondary power supply, and the on-site use is convenient and fast. Can provide DC20 ~ 265V adjustable power supply, current 20A. Arbitrarily set the operating voltage value of the opening and closing coils, and can be used to test the low voltage operation of the circuit breaker.
4. Equipped with linear sensor, rotation sensor, universal sensor and bracket, special fixed multi-function connector, installation is extremely convenient and simple.
5. Applicable to all types of SF6 switches, GIS combined appliances, vacuum switches, oil switches produced at home and abroad.
6. The switch acts once to get all the data and graphics.
7. The host can store six thousand sets of current test data (expandable memory card), and the real-time clock inside the machine is convenient for archiving.
8. Equipped with U disk interface, can directly save data to U disk, upload to computer for analysis and storage.
9. At the same time, it can test 12-channel metal contact fracture, 6-channel closing resistance, and 6-channel graphite contact test.
10. Contains the envelope line. Through the value of multiple (2-10) switch tests, the standard envelope line is generated for analysis and comparison, and the vibration frequency of the switch can be analyzed.
11. The internal anti-interference circuit can meet the reliable use in 500kV substation.
Technical index
1. Time measurement: 12-way inherent opening (closing) time Opening (closing) phases in different phases Opening (closing) different phases Closing (opening) bounce time (number of bounces) Test range: 0.01ms ~ 18000ms, resolution: 0.01ms 2. Closing resistance measurement: 3-way inherent opening (closing) time Opening (closing) phases in different phases Opening (closing) different phases Closing (opening) bounce time (number of bounces) Closing resistance input time 3. Measuring range: 0 ~ 1300Ω, resolution 1Ω, accuracy 1% 4. Graphite contact measurement: 3-way inherent opening (closing) time Opening (closing) phases in different phases Opening (closing) different phases 5. Speed measurement: just divided (just close) speed Average speed in specified time period (travel or angle) 6. Speed measuring range: 1mm sensor 0.01 ~ 25.00m / s 0.1mm sensor 0.001 ~ 2.50m / s 0.5 ° angle sensor 1 cycle / 0.5 ° 7. Stroke measurement: moving contact stroke (stroke) Contact stroke (open distance) Overshoot travel or reverse travel (overtravel) Sensor: 50mm, resolution: 0.1mm 360 line sensor: 360 °, resolution: 0.5 ° Optional sensor: 300mm, 1000mm, acceleration sensor 8. Current: The maximum current output is 20A. 9. AC and DC power supply: AC 220V ± 10%; 50Hz ± 2% 10. DC power supply: output voltage: 35 ~ 265V continuously adjustable, output current: ≤ 20A (short time) 11. Measuring range of isolation switch: Voltage output: DC35 ~ 265V (adjustable) Power output time: 0.01-20 seconds (can be set) The maximum acquisition time of the fracture signal is 20 seconds Measurable fracture closing, opening time, three-phase different period, bounce time and frequency 12. Host volume: 380 × 280 × 170mm 13. Use environment: -10 ℃ ~ + 50 ℃ 14. Relative humidity: ≤90% |
Packaging & Shipping